Rooftop Unit Turns On and Off Frequently

Unit starts and stops every few minutes instead of running complete cooling cycles

Fix Steps:
1
Check thermostat differential setting - should be 1-2°F minimum
2
Verify filter pressure drop - replace if above 0.5 inches water column
3
Check refrigerant charge - improper charge causes short cycling
4
Inspect compressor contactors for pitting or damage
5
Verify high/low pressure switches are functioning correctly
6
Check for oversized equipment relative to load
7
Inspect economizer dampers operate smoothly and seal completely
8
Verify airflow is within manufacturer specifications (CFM per ton)
9
Check all safety controls reset properly
10
Review building automation system settings for conflicts
Preventive Tip

Professional quarterly maintenance. Monitor filter pressure monthly. Check refrigerant charge seasonally. Calibrate controls annually. Log run cycles for trend analysis. Replace contactors every 3-5 years.